Automatic multifuel boiler |
|
|
|
brochure
 
* Value for lower/upper
boiler output in recommended output range, related to CO2 content of 13% and
mean boiler water temperature of 60°C. Stack dimensions must be calculated in
accordance with DIN 4705. |
Heating simply can be cheaper with automatic
multifuel boilers
- At a time of rising fuel costs , the Kroll universal waste oil
boiler, which can burn nearly all vegetable, animal, conventional and waste
oil, will save you money.
- It provides you with flexibility in choosing your perferred fuel source.
|
Kroll
Boiler Figure |
KWOB |
20 |
20T |
35 |
35T |
55 |
55T |
| Output range |
kW |
17-20 |
17-20 |
25-32 |
25-32 |
50-63 |
50-63 |
| Output range in BTU's in 000's |
BTU's |
58-68 |
58-68 |
85-109 |
85-109 |
170-290 |
170-290 |
| Tank capacity |
ltr. |
|
155 |
|
200 |
|
200 |
| Continous output of tank 200 Ltr. |
ltr/h |
|
490 |
|
780 |
|
1225 |
| Output factor 200 Ltr. |
NL |
|
2,8 |
|
4,8 |
|
5 |
| Boiler water content |
ltr. |
51 |
51 |
68 |
68 |
105 |
105 |
| Boiler gas content |
ltr. |
36 |
36 |
61 |
61 |
130 |
130 |
| Hot water resistance (at ∆t=20K ) |
mbar |
6 |
6 |
10 |
10 |
22 |
22 |
| max.permissible boiler pressure |
bar |
3 |
3 |
3 |
3 |
3 |
3 |
| max.permissible
storage tank pressure |
bar |
|
10 |
|
10 |
|
10 |
| Relative boiler
standby loss |
% |
1,6 |
1,6 |
1,1 |
1,1 |
0,7 |
0,7 |
| Required boiler
feed pressure |
Pa |
3 |
3 |
5 |
5 |
8 |
8 |
| Flue-gas
temperature* |
°C |
160-180 |
160-180 |
180-200 |
180-200 |
165-180 |
165-180 |
| Flue-gas mass
flow* |
kg/h |
29-34 |
29-34 |
42-54 |
42-54 |
85-107 |
85-107 |
| Weight boiler |
kg |
135 |
135 |
169 |
169 |
258 |
258 |
| Poids ballon |
kg |
|
66 |
|
83 |
|
83 |
| Diameter of
flue-gas piper |
mm |
129 |
129 |
149 |
149 |
179 |
179 |
| Boiler flow /
boiler return |
G |
1 1/2 |
1 1/2 |
1 1/2 |
1 1/2 |
1 1/2 |
1 1/2 |
| filling emptying |
R |
1 |
1 |
1 |
1 |
1 1/4 |
1 1/4 |
| Vent safety feed
line |
R |
1 |
1 |
1 |
1 |
1 1/4 |
1 1/4 |
| Cold water feed
line/ hot water connection |
R |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
| Storage tank
circulation pipe -200 Ltr. |
R |
|
3/4 |
|
3/4 |
|
3/4 |
| Height of boiler |
A mm |
670 |
670 |
670 |
670 |
845 |
845 |
| Width of boiler
/ storage tank |
B mm |
660 |
660 |
660 |
660 |
760 |
760 |
| Length of boiler |
C mm |
756 |
756 |
876 |
876 |
1056 |
1056 |
| Length of
storage tank 200 Ltr. |
D mm |
|
987 |
|
1262 |
|
1262 |
| Depth of sound
absorbant hood |
E mm |
290 |
290 |
290 |
290 |
290 |
290 |
| Overall height
with control unit |
F1 mm |
1115 |
1115 |
1115 |
1115 |
1635 |
1635 |
| Overall height
with control unit |
F2 mm |
1460 |
1460 |
1460 |
1460 |
1635 |
1635 |
| Flue connection |
G1 mm |
607 |
607 |
607 |
607 |
657 |
657 |
| Flue connection |
G2 mm |
|
952 |
|
952 |
|
1002 |
| Heating
connections |
H mm |
260 |
260 |
260 |
260 |
300 |
300 |
| Heating
connections |
J mm |
326 |
326 |
390 |
390 |
484 |
484 |
| Electrical
connections |
230 V / 50 Hz / 10 A |
|
| |
|
|
|
| |
|


* Figures for upper/lower boiler output in recommended range with a CO2
content of 13% and a mean boiler water temperature of 60 °C
** Overheat safety cutout convertible: 120 °C / 110 °C /
100 °C |
|
Kroll
Boiler Figure |
KWOB |
85 |
100 |
150 |
200 |
| Output range |
kW |
70-85 |
85-99 |
110-160 |
160-200 |
| Output range in BTU's in 000's |
BTU's |
238-290 |
290-338 |
375-511 |
546-682 |
| Height/height without casing |
A mm |
1180/1155 |
1180/1155 |
1180/1155 |
1346/1320 |
| Width/width without casing |
B mm |
794/600 |
794/600 |
794/600 |
974/780 |
| Length |
C mm |
1410 |
1410 |
1760 |
1948 |
| Total height with control system |
D mm |
1335 |
1335 |
1335 |
1500 |
| Length of burner |
E mm |
290 |
290 |
440 |
440 |
| Filling draining |
F mm |
203 |
203 |
203 |
172 |
| Flue-gas pipe connection |
G mm |
922 |
922 |
922 |
1048 |
| Heating return |
H mm |
324 |
324 |
324 |
367 |
| Heating flow |
J mm |
724 |
724 |
1074 |
1117 |
| Expansion flow |
K mm |
874 |
874 |
1224 |
1407 |
| Flue-gas pipe diameter |
mm |
178 |
178 |
195 |
195 |
| Foundation |
mm |
1500x950 |
1500x950 |
2000x1000 |
2000x1000 |
| Filling, draining, expansion return |
R |
1 1/2 " |
1 1/2 " |
1 1/2 " |
1 1/2 " |
| Heating return |
Flange DN |
65 |
65 |
65 |
80 |
| Heating flow |
Flange DN |
65 |
65 |
65 |
80 |
| Expansion flow, vent (ext. thread) |
R |
1 1/4 " |
1 1/4 " |
1 1/4 " |
1 1/2 " |
| Water capacity of boiler |
Ltr. |
216 |
213 |
288 |
508 |
| Gas capacity of boiler |
Ltr. |
140 |
143 |
206 |
333 |
| Heating surface area |
m˛ |
3,5 |
3,8 |
5,2 |
8 |
| Flue-gas resistance * |
mbar |
0,3 |
0,4 |
0,8 |
1,1 |
| Heating water resistance (at t=20k) * |
mbar |
1,2 |
1,7 |
3,5 |
4,5 |
| Max boiler overpressure (gauge) |
bar |
4 |
4 |
4 |
4 |
| Max.permissibler temperature ** |
°C |
120 |
120 |
120 |
120 |
| Relative stand-by loss |
% |
0,7 |
0,7 |
0,6 |
0,5 |
| Flue-gas temperature * |
°C |
145-165 |
145-165 |
145-165 |
145-165 |
| Flue-gas temperature 1st stage |
°C |
120 |
120 |
120 |
120 |
Flue-gas mass flow *
(Flue oil EL CO2 =9,5%) |
kg/h |
127-142 |
142-168 |
184-235 |
269-319 |
Flue-gas mass flow *
(Natural gas E CO2 =9,0%) |
kg/h |
125-151 |
151-178 |
196-249 |
285-338 |
Flue-gas mass flow *
(Natural gas LL CO2 =9,0%) |
kg/h |
129-157 |
157-185 |
203-259 |
269-351 |
Flue-gas mass flow *
(LPG CO2 =11%) |
kg/h |
120-146 |
146-172 |
189-240 |
274-326 |
| Weight |
Boiler kg |
406 |
413 |
524 |
730 |
| Electricity supply |
|
230 V / 50 Hz /
10 A |
|
| |
|

|
Compressor for multi fuel oil burners
| Technical data |
|
for KG/UB 20-100 |
for KG/UB 150-200 |
| Power |
l/min |
80 |
150 |
| Pressure |
bar |
1,5 |
1,5 |
| Current consumption |
A |
2,0 |
4,0 |
| Power consumption |
W |
435 |
770 |
| Voltage |
V~ /H |
230 / 50 |
230 / 50 |
| Weight |
kg |
13,50 |
26 |
|
|
| |
|
|
Kroll Oil delivery system |
| |
|
|
 |
| |
|
|
|
| |
|
|
You will find further information and prices via
information & more or by sending our
E-Mail form.
|
|