Room Sealed Gas Fired Unit Heater

  • for all kinds of gas
  • atmospheric process of combustion and axial ventilator ensure noiseless operation
  • connection either to flue system or on an outer wall

     
Technical Data N 25 N 30 N 40 N 60 N 75
Rated heat load (kW) 24,4 30,9 38,6 52,9 75,0
Rated heating power (kW) 22,0 27,9 34,9 48 68,3
Rated air rate (m3/h) 1900 2950 3250 5300 6600
Rise in temperature (°C Δt) 33 30 34 29 33
Length of throw (m) 16 19 20 23 25
Gas consumption natural gas (m³/h)
                            liquefied gas (kg/h)
2,57
1,86
3,26
2,35
4,08
2,94
5,6
4,03
7,9
5,81
Power connection (Volt/Watt) 230/185 230/220 230/220 230/2x220 230/3x185
Revolutions (r.p.m.) 1300 1300 1300 1300 1300
Noise level (dB) 55 58 58 60 57
Gas connection (") 1/2 1/2 1/2 3/4 3/4
Waste gas duct (Ø mm)
Combustion air connection (Ø mm)
100
130
100
130
100
130
100
150
100
150
Length (mm)
Width (mm)
Height (mm)
635
495
750
745
495
750
865
495
750
1350
495
875
1635
495
900
Weight (kg) 58 70 82 125 190


 

Unit 49, Azura Close • Woolsbridge Industrial Estate • Three Legged Cross • Wimborne • Dorset • BH21 6SZ